BS 5041 PRV FLANGED KITE MARK & KM 632061

. Designed and built in accordance with BS 5041 Part 1:1987
. The Inlet on an Instantaneous Valve is flanged
. Valve is fully complied to all the operational requirement of the standards without alteration of initial settings
. Primary shut – off Valves using a high-quality rubber boned seating disc for a watertight rubber to metal seal
. High Quality Casting Finishes and Corrosion Resistant

Additional information

Body

Copper Alloy to BS 1400 LG 2

Hand Wheel

Grey Cast Iron to BS EN 1561

Inlet

Flanged

Outlet

Female Instantaneous to BS 336:2010

Working Pressure

20 Bar Max

Pressure Rating

High Pressure Valve

Nominal Size

DN 65

Seat Test Pressure

22.5 Bar

Body Test Pressure

30 Bar

Flange Drilling

BS 4504 Part 2:1974

Min. Water Flow Rate

8.5 L/S @ 4 Bar Outlet Pressure

Min. Valve Pressure Regulating

4 to 12 Bar